Compromised Effectiveness of Thermal Inactivation of Legionella pneumophila in Water Heater Sediments and Water, and Influence of the Presence of Vermamoeba vermiformis

Microorganisms. 2022 Feb 15;10(2):443. doi: 10.3390/microorganisms10020443.

Abstract

Intermittent reduction of temperature set-points and periodic shutdowns of water heaters have been proposed to reduce energy consumption in buildings. However, the consequences of such measures on the occurrence and proliferation of Legionella pneumophila (Lp) in hot water systems have not been documented. The impact of single and repeated heat shocks was investigated using an environmental strain of L. pneumophila and a reference strain of V. vermiformis. Heat shocks at temperatures ranging from 50 °C to 70 °C were applied for 1 h and 4 h in water and water heaters loose deposits (sludge). The regrowth potential of heat-treated culturable L. pneumophila in presence of V. vermiformis in water heaters sludges was evaluated. A 2.5-log loss of culturability of L. pneumophila was observed in simulated drinking water at 60 °C while a 4-log reduction was reached in water heaters loose deposits. Persistence of Lp after 4 h at 55 °C was shown and the presence of V. vermiformis in water heater's loose deposits resulted in a drastic amplification (5-log). Results show that thermal inactivation by heat shock is only efficient at elevated temperatures (50 °C) in both water and loose deposits. The few remaining organisms can rapidly proliferate during storage at lower temperature in the presence of hosts.

Keywords: Legionella pneumophila; Vermamoeba vermiformis; flow cytometry; hot water distribution system; temperature; thermal treatment; water heater.