How much natural ventilation rate can suppress COVID-19 transmission in occupancy zones?

J Res Med Sci. 2024 Feb 23:28:84. doi: 10.4103/jrms.jrms_796_22. eCollection 2023.

Abstract

Background: Previous research has emphasized the importance of efficient ventilation in suppressing COVID-19 transmission in indoor spaces, yet suitable ventilation rates have not been suggested.

Materials and methods: This study investigated the impacts of mechanical, natural, single-sided, cross-ventilation, and three mask types (homemade, surgical, N95) on COVID-19 spread across eight common indoor settings. Viral exposure was quantified using a mass balance calculation of inhaled viral particles, accounting for initial viral load, removal via ventilation, and mask filtration efficiency.

Results: Results demonstrated that natural cross-ventilation significantly reduced viral load, decreasing from 10,000 to 0 viruses over 15 minutes in a 100 m2 space by providing ~1325 m3/h of outdoor air via two 0.6 m2 openings at 1.5 m/s wind speed. In contrast, single-sided ventilation only halved viral load at best.

Conclusion: Natural cross-ventilation with masks effectively suppressed airborne viruses, lowering potential infections and disease transmission. The study recommends suitable ventilation rates to reduce COVID-19 infection risks in indoor spaces.

Keywords: COVID-19; mask; natural ventilation; risk of infection; ventilation.