Bio-Inspired PHM Model for Diagnostics of Faults in Power Transformers Using Dissolved Gas-in-Oil Data

Sensors (Basel). 2019 Feb 18;19(4):845. doi: 10.3390/s19040845.

Abstract

Prognostics and Health Management (PHM) is an emerging technique which can improve the availability and efficiency of equipment. A series of related optimization of the PHM system has been achieved due to the growing need for lowering the cost of maintenance. The PHM system highly relies on data collected from its components. Based on the theory of machine learning, this paper proposes a bio-inspired PHM model based on a dissolved gas-in-oil dataset (DGA) to diagnose faults of transformes in power grids. Specifically, this model applies Bat algorithm (BA), a metaheuristic population-based algorithm, to optimize the structure of the Back-propagation neural network (BPNN). Furthermore, this paper proposes a modified Bat algorithm (MBA); here the chaos strategy is utilized to improve the random initialization process of BA in order to avoid falling into local optima. To prove that the proposed PHM model has better fault diagnostic performance than others, fitness and mean squared error (MSE) of Bat-BPNN are set as reference amounts to compare with other power grid PHM approaches including BPNN, Particle swarm optimization (PSO)-BPNN, as well as Genetic algorithm (GA)-BPNN. The experimental results show that the BA-BPNN model has increased the fault diagnosis accuracy from 77.14% to 97.14%, which is higher than other power transformer PHM models.

Keywords: BP neural network; bat algorithm; fault diagnosis; power transformer PHM.