Bioelectromagnetics. 2012 Jul;33(5):438-42. doi: 10.1002/bem.21711. Epub 2012 Feb 14.

Occupational exposure to electric fields and currents associated with 110 kV substation tasks.

Author information

  • 1Environmental Health, Tampere University of Technology, Tampere, Finland. leena.korpinen@tut.fi

Abstract

The main aim of this study was to investigate occupational exposure to electric fields, and current densities and contact currents associated with tasks at air-insulated 110 kV substations and analyze if the action value of EU Directive 2004/40/EC was exceeded. Four workers volunteered to simulate the following tasks: Task (A) maintenance of an operating device of a disconnector at ground or floor level, Task (B) maintenance of an operating device of a circuit breaker at ground or floor level, Task (C) breaker head maintenance from a man hoist, and Task (D) maintenance of an operating device of a circuit breaker from a service platform. The highest maximum average current density in the neck was 1.8 mA/m(2) (calculated internal electric field 9.0-18.0 mV/m) and the highest contact current was 79.4 µA. All measured values at substations were lower than the limit value (10 mA/m(2)) of the EU Directive 2004/40/EC and the 2010 basic restrictions (0.1 and 0.8 V/m for central nervous system tissues of the head, and all tissues of the head and body, respectively) of the International Commission on Non-Ionizing Radiation Protection (ICNIRP).

Copyright © 2012 Wiley Periodicals, Inc.

PMID:
22334373
[PubMed - indexed for MEDLINE]
PubMed Commons home

PubMed Commons

0 comments
How to join PubMed Commons

    Supplemental Content

    Icon for John Wiley & Sons, Inc.
    Loading ...
    Write to the Help Desk