A community-wide outbreak of legionnaires disease linked to industrial cooling towers--how far can contaminated aerosols spread?

Institut de Veille Sanitaire and European Programme for Intervention Epidemiology Training, Saint-Maurice, France. nguyen.tran.minh@ktl.fi

A community-wide outbreak of legionnaires disease occurred in Pas-de-Calais, France, in November 2003-January 2004. Eighteen (21%) of 86 laboratory-confirmed cases were fatal. A case-control study identified smoking, silicosis, and spending >100 min outdoors daily as risk factors for acquiring the disease. Legionella pneumophila strain Lens was isolated from cooling towers, wastewater, and air samples from plant A. This unique strain matched all 23 clinical isolates, as assessed by pulsed-field gel electrophoresis subtyping. Modeling of atmospheric dispersion of aerosols emitted from plant A cooling towers showed good coverage of the communes where patients lived and showed that the dispersion extended over a distance of at least 6 km from plant A. No other aerosol-producing installation was identified as a plausible source, and no common source of indoor exposure was found. These findings implicate plant A as the most likely outbreak source and suggest that the distance of airborne transmission of L. pneumophila may be greater than previously reported.