Legionella pneumophila in Cooling Towers: Fluctuations in Counts, Determination of Genetic Variability by Pulsed-Field Gel Electrophoresis (PFGE), and Persistence of PFGE Patterns[down-pointing small open triangle]

Abstract

The concentrations of Legionella pneumophila in cooling towers may vary considerably over short periods of time, producing significant fluctuations throughout the year. Despite genetic variability, in small geographical areas the same indistinguishable pulsed-field gel electrophoresis patterns may be shared among different cooling towers and persist over time.

The involvement of cooling towers in some community outbreaks of legionellosis has been demonstrated (3, 6, 8, 9, 11), and it has been suggested that there may be an association between high Legionella counts in cooling towers and the occurrence of an outbreak of legionellosis (12). Although not all environmental isolates are associated with human disease, the present guidelines aimed at preventing legionellosis have proposed ranges of risk involving different environmental insults based on Legionella counts (4). However, the fluctuations in Legionella counts over short periods of time have led some authors to question these risk ranges (1).

Since the recovery of a high inoculum of Legionella in a cooling tower is not necessarily related to an outbreak or sporadic cases of legionellosis, genetic studies are necessary to establish the link between environmental and clinical isolates. The “gold standard” technique for genotyping Legionella is the analysis of chromosomal restriction patterns by pulsed-field gel electrophoresis (PFGE). Isolation of Legionella strains from a cooling tower which are genetically indistinguishable from clinical isolates is considered to be clear evidence of the implication of the tower in an outbreak (1, 9). However, little is known regarding the genetic variability of Legionella within the same tower and in cooling towers from areas in the vicinity. Likewise, to our knowledge, no study has determined the persistence of molecular patterns in isolates in cooling towers. All these circumstances have epidemiological and legal consequences when assigning responsibility for an outbreak of legionellosis to a particular installation.

The main objectives of this study were to establish the fluctuations in Legionella counts over time and to determine the genetic variability and persistence of PFGE patterns in cooling towers.

Fifteen cooling towers (A to O) were selected within a radius of 3 km. Four of them (J, K, M, and N) shared the same main line for water distribution. The other cooling towers had a different domestic distribution system but were supplied by the same municipal water network. All the cooling towers followed the controls and hygiene measures required by Spanish regulations (RD 865/2003), and we were able to verify that the levels of disinfectant (sodium hypochlorite [0.2 to 0.5 ppm residual] in conjunction with the discontinuous dosage of nonoxidant biocide [dibromonitrilopropionamide]) were in accordance with legislation at the time of sampling. Cooling water samples were cultured for Legionella fortnightly over a 1-year period. The samples were concentrated by filtration, and four plates of GVPC agar (Oxoid, Wesel, Germany) were seeded from each sample: (i) direct sample with acid pretreatment and (ii) concentrated sample without pretreatment, (iii) concentrated sample with acid pretreatment, and (iv) concentrated sample with heat pretreatment. The plates were incubated at 36°C for 10 days in a moist CO2-enriched atmosphere. Legionella spp. were identified by Gram staining and the pattern of nutritional requirements. An agglutination test (Oxoid) confirmed the identification of the species as L. pneumophila and determined the serogroups.

For chromosomal DNA subtyping 10 Legionella isolates were selected, whenever possible, for each sample. All isolates were analyzed by PFGE as described previously (10). According to the criteria of Tenover et al. (13), chromosomal PFGE patterns differing in one or more bands were considered distinct in this study.

Table Table11 shows the results obtained for Legionella counts. Legionella spp. were isolated in 13 (86.6%) of the 15 towers with the fluctuations in Legionella counts in these towers ranging from <50 CFU/liter (detection limit) to 2,000,000 CFU/liter (Fig. (Fig.1).1). In 75.9% (284/374) of the samples analyzed, the Legionella counts were less than 100 CFU/liter, while counts greater than 10,000 CFU/liter were found in 15% (56/374) of the total. No correlation was found between volumetric and operational differences between cooling towers and bacterial counts. L. pneumophila serogroup 1 and serogroups 2 to 14 were isolated from 13 and 2 cooling towers, respectively (Table (Table2).2). These results confirm and expand those observed by other authors (1) and demonstrate that the concentrations of L. pneumophila in cooling towers may vary considerably over short time periods, producing significant fluctuations throughout the year. These oscillations reflect the dynamism of these ecosystems in which numerous bacterial species, protozoa, and ciliates make up an adherent biofilm (5). These associations contribute to the amplification of the inoculum of Legionella spp. and make them resistant to the biocides used for cleaning and disinfecting these installations (2, 14). The fluctuations observed make it difficult to establish norms and guidelines to specify the minimum sampling periods to maintain a cooling tower under control and to avoid large outbreaks of legionellosis.

FIG. 1.
Geometric mean Legionella counts in each cooling tower. Bars represent the standard deviations.
TABLE 1.
Cooling towers and levels of colonization
TABLE 2.
Serologic identification of the serogroups of L. pneumophila strains and PFGE patterns found in each cooling tower

Sixteen chromosomal restriction patterns determined by PFGE were detected among the isolates from 13 positive cooling towers. The strains of L. pneumophila serogroup 1 exhibited 15 of the 16 different PFGE patterns, while all the strains of serogroups 2 to 14 showed the same PFGE pattern. Five of the 16 PFGE patterns were shared by different cooling towers (Table (Table2).2). As expected, shared PFGE patterns were observed in those cooling towers with the same main water supply, but some of the other cooling towers also exhibited shared PFGE patterns. Hypothetically, when a clone of Legionella from the municipal water network colonizes a cooling tower, it may undergo an adaptation process depending on its ability to respond to the environmental pressure. The environmental pressures leading to the adaptation response may be similar in small areas, which would increase the chance of finding similar PFGE patterns.

On comparing the PFGE patterns of the Legionella isolates from cooling towers which were positive more than once, it was found that these patterns persisted in each cooling tower, at least during the study period.

The concept of clonal variability is of great importance for the epidemiological studies performed when a community outbreak of legionellosis is declared (7). The variability among the isolates from different cooling towers facilitates the determination of the source responsible for an outbreak. Nevertheless, in small areas, some cooling towers can share some of their molecular patterns; therefore, a great number of facilities should be investigated when an outbreak is declared. Moreover, the clonal variability observed within the same cooling tower makes it necessary to undertake molecular analysis of a greater number of isolates from each one.

The persistence of PFGE patterns observed may also be a useful tool in epidemiological studies. Media response to a community outbreak of legionellosis may lead the owners of the installations to attempt disinfection with large quantities of disinfectants before samples are collected by the authorities for epidemiological and molecular studies. In these cases, strains of Legionella cannot be recovered from all the installations that were positive at the time at which the outbreak was declared. However, the persistence of these strains allows their recovery at a later date, thereby providing a resolution to many of the outbreaks which would otherwise have remained unsolved.

Although these cooling towers were not related to any outbreak, at least during the study, we believe that the results obtained may be extrapolated to other strains which have been related to clinical cases. This study offers a perspective on some epidemiological variables when investigating a community outbreak of Legionnaires' disease in a small geographical area. Legionella count variation, genomic variability, shared PFGE patterns, and persistence of Legionella PFGE patterns should be taken into account when cooling towers are the facilities under investigation.

Acknowledgments

This study was supported by grant 03/1501 from Fondo de Investigaciones Sanitarias, Spain.

Footnotes

[down-pointing small open triangle]Published ahead of print on 29 June 2007.

REFERENCES

1. Bentham, R. H. 2000. Routine sampling and the control of Legionella spp. in cooling tower water systems. Curr. Microbiol. 41:271-275. [PubMed]
2. Borella, P., E. Guerrieri, I. Marchesi, M. Bondi, and P. Messi. 2005. Water ecology of Legionella and protozoan: environmental and public health perspectives. Biotechnol. Annu. Rev. 11:355-380. [PubMed]
3. Brown, C. M., P. J. Nuorti, R. F. Breiman, A. L. Hathcock, B. S. Fields, H. B. Lipman, G. C. Llewellyn, J. Hofmann, and M. Cetron. 1999. A community outbreak of Legionnaires' disease linked to hospital cooling towers: an epidemiological method to calculate dose of exposure. Int. J. Epidemiol. 28:353-359. [PubMed]
4. European Surveillance Scheme for Travel Associated Legionnaires' Disease and the European Working Group for Legionella Infections. 2005. European guidelines for control and prevention of travel associated Legionnaires' disease. http://www.ewgli.org/data/european-guidelines/european-guidelines-jan05.pdf.
5. Garcia, M. T., S. Jones, C. Pelaz, R. D. Millar, and Y. Abu Kwaik. 2007. Acanthamoeba polyphaga resuscitates viable non-culturable Legionella pneumophila after disinfection. Environ. Microbiol. 9:1267-1277. [PubMed]
6. Garcia-Fulgueiras, A., C. Navarro, D. Fenoll, J. Garcia, P. González-Diego, T. Jiménez-Buñuales, M. Rodriguez, R. Lopez, F. Pacheco, J. Ruiz, M. Segovia, B. Baladrón, and C. Pelaz. 2003. Legionnaires' disease outbreak in Murcia, Spain. Emerg. Infect. Dis. 9:915-921. [PMC free article] [PubMed]
7. Greig, J. E., J. A. Carnie, G. F. Tallis, N. J. Ryan, A. G. Tan, I. R. Gordon, B. Zwolak, J. A. Leydon, C. S. Guest, and W. G. Hart. 2004. An outbreak of Legionnaires' disease at the Melbourne Aquarium, April 2000: investigation and case-control studies. Med. J. Aust. 180:566-572. [PubMed]
8. Kirrage, D., G. Reynolds, G. E. Smith, and B. Olowokure for the Hereford Legionnaires Outbreak Control Team. 2007. Investigation of an outbreak of Legionnaires' disease: Hereford, UK 2003. Respir. Med. 101:1639-1644. [PubMed]
9. Sabria, M., J. Alvarez, A. Dominguez, A. Pedrol, G. Sauca, L. Salleras, A. Lopez, M. A. Garcia-Nuñez, I. Parron, and P. Barrufet. 2006. A community outbreak of Legionnaires' disease: evidence of a cooling tower as the source. Clin. Microbiol. Infect. 12:642-647. [PubMed]
10. Sabria, M., M. García-Nuñez, M. L. Pedro-Botet, N. Sopena, J. M. Gimeno, E. Reynaga, J. Morera, and C. Rey-Joly. 2001. Presence and chromosomal subtyping of Legionella species in potable water systems in 20 hospitals of Catalonia, Spain. Infect. Control Hosp. Epidemiol. 22:673-676. [PubMed]
11. Sala, M. R., C. Arias, J. M. Oliva, A. Pedrol, P. Roura, and A. Dominguez. 2007. Community outbreak of Legionnaires disease in Vic-Gurb, Spain in October and November 2005. Euro Surveill. 12:223. [PubMed]
12. Shelton, B. G., W. D. Flanders, and G. K. Morris. 1994. Legionnaires' disease outbreaks and cooling towers with amplified Legionella concentrations. Curr. Microbiol. 28:359-363.
13. Tenover, F. C., R. D. Arbeit, R. V. Goering, P. A. Mickelsen, B. E. Murray, D. H. Persing, and B. Swaminathan. 1995. Interpreting chromosomal DNA restriction patterns produced by pulsed-field gel electrophoresis: criteria for bacterial strain typing. J. Clin. Microbiol. 33:2233-2239. [PMC free article] [PubMed]
14. Winiecka-Krusnell, J., and E. Linder. 1999. Free-living amoebae protecting Legionella in water: the tip of an iceberg? Scand. J. Infect. Dis. 31:383-385. [PubMed]

Articles from Applied and Environmental Microbiology are provided here courtesy of American Society for Microbiology (ASM)
PubReader format: click here to try

Formats:

Related citations in PubMed

See reviews...See all...

Cited by other articles in PMC

See all...

Links

Recent Activity

Your browsing activity is empty.

Activity recording is turned off.

Turn recording back on

See more...